History — 303.09

Every captured version of this section, newest first. Word-level diffs show exactly what each amendment changed. Read the current text →

FIRST SEENsnapshot of 2026-03-01 · consolidation amended to 2025-12-09
Text as first captured
303.09 Subject to sections 303.10 and 303.11, the operator of a designated airport or of a participating airport or aerodrome the critical category for fire fighting of which is set out in column I of an item of the table to this section shall provide to the aircraft fire-fighting service at the airport or aerodrome the quantities of water and complementary extinguishing agents set out in columns II and III of the item, and the minimum number of aircraft fire-fighting vehicles set out in column IV of that item necessary to provide the total discharge capacity set out in column V of that item. TABLE Column I Column II Column III Column IV Column V Item Critical Category for Fire Fighting Quantity of Water (in litres) Quantity of Complementary Extinguishing Agents (in kilograms) Minimum Number of Aircraft Fire-fighting Vehicles Total Discharge Capacity (in litres per minute) 1 1 230 45 1 230 2 2 670 90 1 550 3 3 1 200 135 1 900 4 4 2 400 135 1 1 800 5 5 5 400 180 1 3 000 6 6 7 900 225 2 4 000 7 7 12 100 225 2 5 300 8 8 18 200 450 3 7 200 9 9 24 300 450 3 9 000 10 10 32 300 450 3 11 200 SOR/97-518, s. 2